| Sign In | Join Free | My qualitytoyschina.com |
|
AC Current Power : 400 VA
Model Number : SXZB-6600
AC Voltage : 0–125 V
MOQ : 1
AC Current : 0–30 / 40 A per phase
Brand Name : Sansion Power
Delivery Time : 30 Working Days
Time Measurement : 0.1 ms–9999 s
Payment Terms : L/C,T/T
Packaging Details : Plywood Case
Current Frequency : 20–500 Hz
Certification : CE/SGS/EMS/ISO 9001
DC Current : 0–±10 A per phase
Place of Origin : China
6 Phase Relay Protection Tester
Designed for modern relay protection testing, the SXZB Series Digital Relay Protection Test System provides AC and DC current and voltage outputs for evaluating protective relay operation. It is intended for electrical power system testing, relay commissioning and maintenance where flexible test signal generation is required.
The system adopts a high-speed DSP processor, true 16-bit DAC and high-power high-fidelity amplifier, together with an industrial computer display and rotary control device. Engineers can perform signal injection and switching-related tests while using the integrated timing measurement function to evaluate relay response during commissioning and maintenance work.
|
Item |
Specification |
|
AC Current |
0–30 / 40 A per phase |
|
AC Current Power |
400 VA |
|
Current Frequency |
20–500 Hz |
|
Current Harmonics |
1–9th |
|
DC Current |
0–±10 A per phase |
|
AC Voltage |
0–125 V |
|
AC Voltage Power |
80 VA |
|
DC Voltage Power |
100 VA |
|
Voltage Frequency |
20–500 Hz |
|
Voltage Harmonics |
1–9th |
|
DC Voltage Amplitude |
0–±140 V |
|
Switch Input |
Dry Contact: 1–20 mA, 24 V |
|
Potential Input |
“0": 0–6 V; “1": +11–250 V |
|
Switch Output |
DC: 220 V / 0.2 A; AC: 220 V / 0.5 A |
|
Time Measurement |
0.1 ms–9999 s |
|
Input Power |
AC 220 V ±10%, 50/60 Hz |
1. Is this a relay protection test system or a general electrical tester?
The SXZB is specifically designed as a relay protection test system for protective relays and relay protection devices.
2. What type of output signals does it provide?
It provides AC/DC current and AC/DC voltage outputs within the specified output ranges.
3. Can it measure test time?
Yes. The system provides a time measurement range of 0.1 ms–9999 s.
4. Can the system be connected to a laptop?
Yes. The product supports connection to a laptop computer in addition to standalone operation.

|
|
6 Phase Relay Protection Test System for Power Utility Relay Testing and Maintenance Images |